| #P001 | physical | operational | mandatory | effect on river level | other | requirement | < 3 cm | Exceptions to the application of the Act if there are insignificant effects on river levels at the Canada - United States boundary. | at the Canadian boundary | high |
| #P002 | physical | operational | mandatory | effect on river flow | other | requirement | < 0.3 cubic metres per second | Exceptions to the application of the Act if there are insignificant effects on river flows at the Canada - United States boundary. | at the Canadian boundary | high |
| #P003 | chemical | health | mandatory | Cadmium AMEL (Freshwater, Hardness up to 200 mg/L) | wastewater, aquatic life | requirement | 3.5 μg/L | Average monthly effluent limitation for cadmium in freshwater inland surface waters based on hardness. | Receiving water total hardness up to 200 mg/L | high |
| #P004 | physical | treatment | mandatory | Total Suspended Solids AMEL (Freshwater MUN) | wastewater, drinking water | requirement | 30 mg/L | Average monthly effluent limitation for TSS in freshwater inland surface waters with MUN beneficial use. | Applicable to all dischargers to freshwater with MUN use. | high |
| #P005 | physical | treatment | mandatory | pH (Freshwater MUN) | wastewater, aquatic life, drinking water | requirement | 6.5 - 8.5 standard units | Instantaneous maximum and minimum pH requirements for freshwater inland surface waters. | pH shall remain within the limits at all times. | high |
| #P006 | chemical | treatment | mandatory | Total Nitrogen Instantaneous Maximum (Freshwater MUN) | wastewater, aquatic life | requirement | 2.0 mg/L | Instantaneous maximum limit for total nitrogen based on reasonable potential analysis. | Applies to freshwater inland surface waters with MUN use. | high |
| #P007 | microbiological | health | mandatory | Total Coliform 30-day Geometric Mean (Bays and Estuaries) | recreational water | requirement | 1000 Organisms/100 mL | Bacterial effluent limitations for discharges to bays and estuaries not including Buena Vista Lagoon. | 30-day geometric mean requirement. | high |
| #P008 | microbiological | health | mandatory | Enterococcus Single Sample Maximum (Bays and Estuaries) | recreational water | requirement | 104 Organisms/100 mL | Single sample maximum bacterial effluent limitation for discharges to bays and estuaries. | Single sample maximum requirement. | high |
| #P009 | chemical | health | mandatory | Copper AMEL (Freshwater, Hardness up to 200 mg/L) | wastewater, aquatic life | requirement | 14 μg/L | Average monthly effluent limitation for copper in freshwater inland surface waters based on hardness. | Receiving water total hardness up to 200 mg/L | high |
| #P010 | chemical | health | mandatory | Copper AMEL (Chollas Creek, Hardness up to 200 mg/L) | wastewater, aquatic life | requirement | 11.6 μg/L | Hardness-dependent metal limitations specifically for Chollas Creek. | Receiving water total hardness up to 200 mg/L | high |
| #P011 | physical | treatment | mandatory | Settleable Solids AMEL (Freshwater MUN) | wastewater | requirement | 0.1 ml/L | Average monthly effluent limitation for settleable solids in Freshwater MUN discharges. | Applicable to all dischargers to freshwater with MUN beneficial use. | high |
| #P012 | chemical | treatment | mandatory | Total Residual Chlorine MDEL (Freshwater MUN) | wastewater, aquatic life | requirement | 8.0 μg/L | Maximum daily effluent limitation for chlorine based on reasonable potential analysis. | Applies if groundwater extraction activity shows reasonable potential. | high |
| #P013 | microbiological | health | mandatory | Enterococcus 30-day geometric mean (Bays and Estuaries) | recreational water | requirement | 35 Organisms/100 mL | Bacteria effluent limitations for discharges to bays and estuaries. | 30 day geometric mean | high |
| #P014 | chemical | health | mandatory | Un-ionized ammonia receiving water limit | aquatic life | requirement | <= 0.025 mg/l as N | The discharge of wastes shall not cause concentrations of un-ionized ammonia (NH3) to exceed this value in inland surface waters. | Applicable to inland surface waters | high |
| #P015 | design | operational | mandatory | Application Threshold - Influent Volume | wastewater | requirement | >= 100 m3 | Average daily volume of influent threshold for regulation applicability. | Deposit to water frequented by fish or place reaching such water. | high |
| #P016 | physical | operational | mandatory | Application Threshold - Geographic (North) | wastewater | requirement | 54 degrees | The Regulations do not apply north of the 54th parallel in Québec or Newfoundland and Labrador. | Specific to QC and NL. | high |
| #P017 | operational | reporting | mandatory | Identification Report Deadline | wastewater | requirement | 45 days | Deadline to submit identification report after system comes into operation. | New wastewater systems. | high |
| #P018 | operational | reporting | mandatory | Change Notification Deadline | wastewater | requirement | 45 days | Deadline to submit changes or new information on the wastewater system. | Applicable after any change in system info. | high |
| #P019 | operational | reporting | mandatory | Reporting Frequency - Quarterly | wastewater | requirement | 4 times a year | Reporting frequency for quarterly reporters. | Determined by system type and size. | high |
| #P020 | operational | reporting | mandatory | Reporting Frequency - Annual | wastewater | requirement | 1 time a year | Reporting frequency for annual reporters. | Determined by system type and size. | high |
| #P021 | operational | reporting | mandatory | Annual Monitoring Report Deadline | wastewater | requirement | February 14 date | Deadline for annual monitoring reports covering Jan 1 to Dec 31. | Annual reporters. | high |
| #P022 | operational | reporting | mandatory | Combined Sewer Overflow Reporting frequency | wastewater | requirement | 1 time per year | Submission frequency for combined sewer overflow reports. | Systems with at least one combined sewer overflow point. | high |
| #P023 | operational | reporting | mandatory | Combined Sewer Overflow Report Deadline | wastewater | requirement | February 15 date | Annual deadline for combined sewer overflow reports. | Systems with overflow points. | high |
| #P024 | operational | reporting | mandatory | Combined Sewer Overflow Deposit Threshold | wastewater | requirement | >= 1 overflow point | Trigger for combined sewer overflow reporting requirement. | Report required for each month where a deposit occurred. | high |
| #P025 | operational | reporting | mandatory | Quarterly Reporting Deadline - Q1 | wastewater | requirement | May 15 date | Deadline for owners or operators of wastewater systems that report four times a year for Quarter 1 (January 1 to March 31). | Quarterly reporters only | high |
| #P026 | operational | reporting | mandatory | Quarterly Reporting Deadline - Q2 | wastewater | requirement | August 14 date | Deadline for owners or operators of wastewater systems that report four times a year for Quarter 2 (April 1 to June 30). | Quarterly reporters only | high |
| #P027 | operational | reporting | mandatory | Quarterly Reporting Deadline - Q3 | wastewater | requirement | November 14 date | Deadline for owners or operators of wastewater systems that report four times a year for Quarter 3 (July 1 to September 30). | Quarterly reporters only | high |
| #P028 | operational | reporting | mandatory | Quarterly Reporting Deadline - Q4 | wastewater | requirement | February 14 date | Deadline for owners or operators of wastewater systems that report four times a year for Quarter 4 (October 1 to December 31). | Quarterly reporters only | high |
| #P029 | design | operational | mandatory | Wastewater System Application Threshold - Influent Volume | wastewater | requirement | >= 100 m3/day | Average daily volume of influent threshold for regulation applicability. | System must deposit wastewater effluent to water frequented by fish or to a place that could reach these waters. | high |
| #P030 | physical | operational | mandatory | Geographic Application Limit (North) | wastewater | requirement | 54 degrees | The Regulations do not apply north of the 54th parallel in Québec or Newfoundland and Labrador. | Specific to QC and NL. | high |
| #P031 | operational | reporting | mandatory | Identification Report Submission Deadline | wastewater | requirement | 45 days | Owners or operators must submit an identification report within 45 days after their system comes into operation. | New systems. | high |
| #P032 | operational | reporting | mandatory | Information Change Notification Deadline | wastewater | requirement | 45 days | Any changes or new information on the wastewater system must be submitted within 45 days of the change. | | high |
| #P033 | operational | reporting | mandatory | Quarterly Reporting Frequency | wastewater | requirement | 4 times a year | Wastewater systems report either once a year or four times a year. | System type and size determines frequency. | high |
| #P034 | operational | reporting | mandatory | Annual Reporting Frequency | wastewater | requirement | 1 time a year | Wastewater systems report either once a year or four times a year. | System type and size determines frequency. | high |
| #P035 | design | operational | mandatory | Combined Sewer Overflow Trigger | wastewater | requirement | >= 1 overflow point | Owners or operators of wastewater systems with at least one combined sewer overflow point. | | high |