Document ID ca-mb-pdvdlpdtdteep-2021-03-4 Title PROCÉDURE DE VALIDATION DE LA PERFORMANCE DES TECHNOLOGIES DE TRAITEMENT EN EAU POTABLE URL https://www.gov.mb.ca/sd/pubs/water/drinking_water/factsheet_nitrate.pdf Jurisdiction /ca/mb Subdomain(s) Regulations & standards Language en Status completed Analyzed at 2026-04-15 01:32:19.468685+00:00 Relevance Provides drinking water standards and guidance for private well owners.

Q Qualitative Requirements (52)

Req ID Category Intent Legal Status Name Subdomain(s) Context Conditions Confidence
#Q001corrective_actionhealthrecommendedCorrective Action for High Nitrate in Private Wellsdrinking waterPrivate well owners are not legally required to meet the standard but where levels are high, a treatment device or other corrective action is recommended.Where nitrate levels are high in private wellshigh
#Q002prohibitionhealthrecommendedProhibition of Infant Formula Preparationdrinking waterWater high in nitrate should not be used to prepare infant formula and should not be given to infants to drink.When water is high in nitratehigh
#Q003prohibitionhealthrecommendedAvoidance by Nursing and Pregnant Womendrinking waterAs nitrate may be present in breast milk or transported through the placenta, nursing mothers and pregnant women should also avoid drinking water high in nitrate.When water is high in nitratehigh
#Q004monitoringhealthguidancePrivate Well Owner Testing Responsibilitydrinking waterPrivate well owners are responsible for testing and, if necessary, treating their water to ensure it is safe to drink.high
#Q005monitoringhealthrecommendedConditions for Nitrate Testingdrinking waterWell water should be tested for nitrate if: someone who drinks the water is pregnant, nursing or planning a pregnancy; there is an infant or toddler less than a year old drinking the water; sources of nitrate are present in the area or the area is known to have elevated nitrate levels; the well is old, shallow or poorly constructed; contamination of the groundwater is suspectedhigh
#Q006monitoringhealthrecommendedWell Retesting Frequencydrinking waterWells should be retested every three to five years or whenever there is a change in the taste, smell, colour or clarity of the well water, or if there is a reason to believe the water quality has changed.high
#Q007monitoringhealthrecommendedIncreased Testing in High-Risk Areasdrinking waterIn areas where nitrate is a concern, well owners should consider testing for nitrate more often.Areas where nitrate is a concernhigh
#Q008monitoringhealthrecommendedSeasonal Variability Testingdrinking waterIf nitrate is at or near guidelines levels, well owners should consider testing at different times of year to get a better understanding of seasonal variability.If nitrate is at or near guidelines levelshigh
#Q009monitoringhealthmandatoryPublic Water System Testingdrinking waterPublic (municipal) water systems that use well water are tested regularly by the water system owner or by the Office of Drinking Water as required under The Drinking Water Safety Act .Public (municipal) water systemshigh
#Q010monitoringoperationalrecommendedSample Collection Proceduredrinking waterWell owners should use the bottle(s) provided by the laboratory and should collect samples carefully, following the instructions provided.high
#Q011corrective_actionhealthrecommendedConsultation with Public Healthdrinking waterIf the nitrate level in the well water is above the drinking water standard, private well owners should consider how they are using this water and may wish to contact their local public health office or discuss health risks with their doctorIf nitrate level is above the drinking water standardhigh
#Q012corrective_actionhealthrecommendedFind Alternative Safe Water Sourcedrinking water1. Find another safe source of drinking water. Do not use the well water for preparing infant formula. Bottled water can be used until a long-term safe water supply is identifiedIf nitrate level is above the drinking water standardhigh
#Q013monitoringhealthrecommendedBacteria Testing Following High Nitratedrinking water2. Test the well for bacteria. Nitrate is an indicator of potential contamination from human or animal waste, and bacteria may be present as well.If nitrate level is above the drinking water standardhigh
#Q014monitoringhealthrecommendedNitrate Retesting Following High Resultdrinking water3. Re-test the well water for nitrate. Nitrate levels can change.If nitrate level is above the drinking water standardhigh
#Q015corrective_actionoperationalrecommendedWell Inspection and Maintenancedrinking water4. Inspect the well. Wells should be constructed and maintained to minimize the risk of contamination. Ensure the well has a secure, watertight cap/lid and that the ground slopes away from the well.If nitrate level is above the drinking water standardhigh
#Q016corrective_actionhealthrecommendedRemoval or Reduction of Nitrate Sourcesdrinking water5. Remove or reduce sources of nitrate if present: Avoid over-application of fertilizers. Do not apply fertilizers near the well. Have your septic system inspected and repaired, if required. Ensure manure or other animal or plant waste materials are not stored or applied near the well.If nitrate level is above the drinking water standardhigh
#Q017corrective_actionhealthrecommendedLong-term Safe Water Supply Considerationdrinking water6. Consider options for ensuring a long-term safe water supply, such as: hooking up to a public (municipal) piped water system if one is available in the area; installing a water cistern and arranging for the delivery of safe drinking water by a water hauler; drilling a new well at a different location or to a different depth. This may or may not solve a nitrate problem. Manitoba Water Stewardship can be consulted for advice; using commercially bottled water from a supplier who is a member of the Canadian Bottled Water Association or International Bottled Water Association; treating the well waterIf nitrate level is above the drinking water standardhigh
#Q018designtreatmentrecommendedTreatment Device Certificationdrinking waterThe treatment device should be certified to meet the NSF International (NSF)/American National Standards Institute (ANSI) standard for removal of nitrate.When installing a water treatment device for nitrate removalhigh
#Q019operationaltreatmentmandatoryTreatment Device Maintenancedrinking waterOnce installed, manufacturer's instructions on the use and maintenance of treatment devices and disposal of filter media should be followed.After installing a treatment devicehigh
#Q020monitoringtreatmentrecommendedAnnual Testing of Treated Waterdrinking waterThe well water and treated drinking water should be tested annually for nitrate to confirm that the treatment system is working properly.When using a treatment device to remove nitratehigh
#Q021administrativereportingmandatoryMELCC Authorization Requirementdrinking waterL'utilisation d'une telle technologie de traitement doit faire l'objet d'une autorisation auprès du MELCC avant d'être mise en place et le formulaire de demande d'autorisation est disponible sur son site Web.For technologies at the 'En validation' levelhigh
#Q022monitoringoperationalmandatoryPilot Test Durationdrinking waterL'unité pilote doit être exploitée dans les conditions de référence durant une période d'au moins 13 semaines en continu où, dans le cas des eaux de surface, les conditions de qualité de l'eau brute sont représentatives des variations anticipées en conditions réelles.For obtaining an 'En validation' certificatehigh
#Q023monitoringreportingmandatoryThird-Party Pilot Supervisiondrinking waterLe suivi des essais pilotes devra être effectué sous la supervision d'une tierce partie compétente comptant au moins un ingénieur qui possède les connaissances nécessaires au suivi de la technologie de traitement.Pilot testing supervisionhigh
#Q024monitoringreportingmandatoryAccredited Laboratory Analysisdrinking waterCe suivi doit être effectué par une tierce partie et les analyses doivent être réalisées par un laboratoire accrédité par le Centre d'expertise en analyse environnementale du Québec (CEAEQ).Analysis of samples during validation monitoringhigh
#Q025administrativereportingmandatoryDocumentation Submission for Level 'En Validation'drinking waterPour que la performance d'une technologie de traitement puisse être validée... le demandeur doit soumettre au BNQ en pièces justificatives au dossier les documents suivants : rapport d'ingénierie conforme à l'annexe 1... rapport de suivi des essais pilotes conforme à l'annexe 2-A... déclaration d'indépendance de la tierce partie; pièces justificatives énumérées dans la procédure BNQ 9922-200.Application for 'En validation' levelhigh
#Q026monitoringoperationalmandatoryFull-Scale Validation Durationdrinking waterLa démonstration doit être basée sur les résultats d'un suivi de validation effectué, pendant une période minimale de 52 semaines consécutives, sur une installation à l'échelle réelle.To obtain a 'Validé' certificatehigh
#Q027prohibitionoperationalmandatoryProhibition of Applicant as Operatordrinking waterLe demandeur de la technologie de traitement ne peut être chargé de l'exploitation.During the full-scale validation monitoring periodhigh
#Q028administrativereportingmandatoryEngineering Report Signatorydrinking waterLe rapport d'ingénierie du demandeur doit être préparé et signé par un ingénieur membre d'un ordre professionnel de la province ou de l'État où il exerce.Applies to all validation requestshigh
#Q029designtreatmentmandatoryUV Reactor Biodosimetry Validationdrinking waterLa performance de tout réacteur de désinfection par irradiation UV utilisé pour le traitement d'eau destinée à la consommation humaine doit avoir été validée par une méthode de biodosimétrie reconnue.UV reactors for drinking waterhigh
#Q030operationaloperationalmandatoryMembrane Filtration Alarm Requirementsdrinking waterLes procédés de traitement par filtration membranaire devront prévoir des alarmes pour les situations suivantes : non-respect de l'intégrité... perte de perméabilité... perte de charge en prétraitement... perte de charge en filtration membranaire... turbidité supérieure ou égale à 0,1 UTN... pression à l'entrée... arrêt du système en raison d'une panne de courant... débits... supérieurs aux seuils.Membrane filtration installationshigh
#Q031designhealthmandatoryMaterials Certification Requirementdrinking waterles matériaux en contact avec l'eau utilisés par la technologie de traitement doivent être certifiés NSF/ANSI 61 ou certifiés aux normes du BNQ appropriées;All water treatment technologieshigh
#Q032designhealthmandatoryTreatment Chemicals Certificationdrinking waterles produits chimiques utilisés dans les technologies de traitement doivent être certifiés NSF/ANSI 60.All chemicals used in treatment technologieshigh
#Q033reportingreportingmandatoryStatistical Significance Requirementdrinking waterIl est requis que l'analyse statistique des résultats démontre que l'allégation de performance est statistiquement significative à 95 %.All performance validation claimshigh
#Q034operationaloperationalmandatoryMaximum Capacity Operational Testingdrinking waterDans le cas où la technologie de traitement est utilisée pour traiter de l'eau de surface, les équipements doivent fonctionner au maximum de leur capacité de production (critères de conception) pendant une période minimale de cinq jours consécutifs à quatre moments précis au cours des 52 semaines de suivi : en hiver, au printemps (en ciblant les pires conditions d'eau brute), en été et à l'automne (en ciblant les pires conditions d'eau brute).Surface water treatment technologies during 52-week validationhigh
#Q035prohibitionoperationalmandatoryProhibition of Trial Modificationsdrinking waterLors d'un essai pilote, aucune modification à la technologie de traitement ne doit être apportée à l'installation. Si une modification est apportée, le suivi des essais pilotes doit se poursuivre pendant au moins 13 semaines en continu après la modification.During pilot trialshigh
#Q036reportingreportingmandatoryNotification of Monitoring Deviationsdrinking waterSi le suivi demandé par le présent document, ou celui soumis et accepté par le BNQ, ne peut être respecté pendant la durée des essais, le demandeur doit communiquer le plus rapidement possible avec le BNQ afin d'obtenir un accord sur les changements à apporter,When monitoring protocol cannot be respectedhigh
#Q037monitoringreportingmandatoryMaintenance of Event Registerdrinking waterLa tierce partie doit tenir un registre des conditions en vigueur à l'échantillonnage, de la chronologie des événements et des interventions effectuées sur l'installation de traitement.During full-scale validation monitoringhigh
#Q038administrativereportingmandatoryIngénieur Attestation for Operating Guidedrinking waterFournir l'attestation d'un ingénieur indiquant que les recommandations d'utilisation, d'inspection et d'entretien formulées dans le guide d'utilisation respectent les règles de l'art, visent à permettre le maintien des performances attendues et concordent avec les activités d'exploitation effectuées lors du suivi des équipements.Applicable to the engineering report for all levelshigh
#Q039prohibitionoperationalmandatoryProhibition of Level 'Validé' Modificationsdrinking waterLors d'un suivi de validation, aucune modification à la technologie de traitement ne doit être apportée à l'installation. Si une modification est apportée, le suivi de validation doit se poursuivre pendant au moins 52 semaines après la modification.During the 52-week full-scale validation periodhigh
#Q040reportingreportingmandatoryProtocol Preparation Requirementdrinking waterLe demandeur doit préparer un protocole d'essai pour le suivi en tenant compte des balises de la présente annexe, en l'adaptant, au besoin, en fonction de la technologie de traitement et de son application.Required before pilot testing for Level 'En validation'high
#Q041reportingreportingmandatoryUV Biodosimetry Justification Reportdrinking waterle demandeur devra soumettre, avec le rapport des essais de biodosimétrie réalisés par une tierce partie indépendante suivant un protocole reconnu, un rapport signé par un ingénieur présentant de façon explicite, à l'aide de chiffriers incluant les formules de calculs et toutes les notes pertinentes, les justifications de chacune des valeurs qu'il souhaite voir présenter pour le réacteur dans la fiche d'information technique.Mandatory for UV reactor performance validationhigh
#Q042operationaltreatmentrecommendedTreatment Device Maintenance Instruction Compliancedrinking waterOnce installed, manufacturer's instructions on the use and maintenance of treatment devices and disposal of filter media should be followed.After installing a treatment devicehigh
#Q043administrativeoperationalrecommendedTreatment Equipment Procurement Quotesdrinking waterQuotes should be obtained from reputable water treatment equipment suppliers.When considering options for water treatmenthigh
#Q044administrativereportingrecommendedSupplier Information Disclosuredrinking waterThe supplier should provide information on how much nitrate will be removed, maintenance requirements and costs.When obtaining quotes from water treatment equipment suppliershigh
#Q045administrativeoperationalrecommendedLaboratory Cost Estimate Requestdrinking waterwell owners should contact the laboratories directly for an estimate.Prior to testing well water for nitratehigh
#Q046reportingreportingmandatoryReddition de comptes annuelledrinking waterLe Ministère leur demande de lui fournir une reddition de comptes annuelle visant à mettre à jour l'état des points d'eau potable utilisés aux fins de consommation.S'applique aux organismes scolaires et établissements d'enseignement privés pour les points d'eau non conformes connushigh
#Q047operationalhealthmandatoryRinçage préventif immédiatdrinking waterFaire couler l'eau au moins une minute avant de la consommerLorsque la concentration du premier échantillon (P0s) est supérieure à 5 µg/L mais celle du second (P30s) est inférieure à 5 µg/Lhigh
#Q048operationalhealthmandatoryCondamnation du point d'eaudrinking waterCondamner le point d'eauLorsque la concentration du second échantillon (P30s) est supérieure à 5 µg/Lhigh
#Q049monitoringoperationalmandatoryVérification de conformité post-correctiondrinking waterLes points d'eau corrigés sont considérés conformes après vérification selon la procédure de dépistage appliquée.Après la mise en place de correctifs sur un point d'eauhigh
#Q050corrective_actiontreatmentmandatoryInterventions correctives à moyen et long termedrinking waterLe Ministère demande aux organismes scolaires de continuer à mettre en place des interventions correctives à moyen terme (installation de filtres anti-plomb) et à long terme (remplacement de plomberie) pour corriger définitivement tous les points d'eau jugés non conformes.Responsabilité continue des organismes scolaires pour les points d'eau non conformeshigh
#Q051monitoringoperationalmandatoryProtocole d'échantillonnage P0s et P30sdrinking waterdeux échantillons d'eau successifs devaient être prélevés à chaque point d'eau pour la mesure de la concentration de plomb, soit : P0s : 1 er jet sans écoulement après au moins 6 heures de stagnation; P30s : après 30 secondes d'écoulement continu.Procédure de mesure des concentrations de plombhigh
#Q052operationaloperationalmandatoryResponsabilité de réalisation continue des travauxdrinking waterLes organismes scolaires étant responsables de réaliser de manière continue les travaux correctifs requisGestion continue des points d'eau non conformeshigh

P Quantitative Requirements (38)

Req ID Category Intent Legal Status Name Subdomain(s) Limit Type Limit Value Context Conditions Confidence
#P001chemicalhealthmandatorynitratedrinking waterMAC45 mg/LHealth Canada has established a maximum acceptable concentration (MAC) for nitrate in drinking water. The provincial standard for all public (municipal) drinking water supplies is 45 mg/L nitrate.Private well owners are not legally required to meet the standard but where levels are high, a treatment device or other corrective action is recommended.high
#P002chemicalhealthmandatorynitrate-nitrogendrinking waterMAC10 mg/L45 mg/L nitrate is equal to 10 mg/L nitrate-nitrogen. The provincial standard for all public (municipal) drinking water supplies is 45 mg/L nitrate (10 mg/L nitrate-nitrogen).Private well owners are not legally required to meet the standard.high
#P003chemicalhealthrecommendednitritedrinking waterrequirement<= 3.2 mg/Lthe Health Canada Guideline recommends nitrite not exceed 3.2 mg/LWhere nitrate and nitrite are measured separatelyhigh
#P004chemicalhealthrecommendednitrite-nitrogendrinking waterrequirement<= 1 mg/Lapproximately 1 mg/L nitrite-nitrogenWhere nitrate and nitrite are measured separatelyhigh
#P005operationaloperationalmandatoryDurée minimale des essais pilotes (Niveau En validation)drinking waterrequirement>= 13 semainesL'unité pilote doit être exploitée dans les conditions de référence durant une période d'au moins 13 semaines en continu.S'applique pour l'obtention d'une fiche de niveau En validation.high
#P006operationaloperationalmandatoryDurée minimale du suivi de validation (Niveau Validé)drinking waterrequirement>= 52 semainesLa démonstration doit être basée sur les résultats d'un suivi de validation effectué, pendant une période minimale de 52 semaines consécutives, sur une installation à l'échelle réelle.S'applique pour l'obtention d'une fiche de niveau Validé.high
#P007operationaloperationalmandatorySeuil de signification statistiquedrinking waterrequirement95 %Il est requis que l'analyse statistique des résultats démontre que l'allégation de performance est statistiquement significative à 95 %.high
#P008chemicaltreatmentmandatoryChlore résiduel libre (Simulation SDS)drinking waterrequirement0.5 +/- 0.2 mg/LEssai de 24 h avec 0,5 ± 0,2 mg/L de chlore résiduel libre après 24 h.Pour les simulations de formation des trihalométhanes (SDS-THM) et acides haloacétiques (SDS-AHA).high
#P009operationaltreatmentmandatoryDurée de l'essai de simulation SDSdrinking waterrequirement24 hConditions standard pour les essais SDS-THM et SDS-AHA.high
#P010physicaltreatmentmandatoryTempérature de l'essai de simulation SDSdrinking waterrequirement+/- 22 °CConditions standard pour les essais SDS-THM et SDS-AHA.high
#P011chemicaltreatmentmandatorypH de l'essai de simulation SDSdrinking waterrequirement7.5 nullConditions standard pour les essais SDS-THM et SDS-AHA.high
#P012operationaloperationalmandatoryDurée des essais pour modification de fichedrinking waterrequirement>= 2 semainesLa demande doit être soutenue par les résultats d'essais pilotes s'étendant sur au moins deux semaines.Pour une demande de modification d'une fiche existante visant un paramètre critique.high
#P013physicaloperationalmandatorySeuil d'alarme de turbidité (Membranes)drinking waterrequirement>= 0.1 UTNLes procédés de traitement par filtration membranaire devront prévoir des alarmes pour les situations suivantes : turbidité supérieure ou égale à 0,1 UTN à la sortie d'une unité.high
#P014operationaloperationalmandatoryPériode de test à capacité maximale (Eaux de surface)drinking waterrequirement>= 5 joursLes équipements doivent fonctionner au maximum de leur capacité de production pendant une période minimale de cinq jours consécutifs à quatre moments précis au cours des 52 semaines.Durant l'hiver, le printemps, l'été et l'automne (en ciblant les pires conditions).high
#P015physicaloperationalmandatoryTurbidité de l'eau brute - Centiledrinking waterrequirement95 e centileValeur basée sur le 95e centile des valeurs observées pour la turbidité à l'eau brute.Eaux de surface.high
#P016chemicaloperationalmandatoryCOT de l'eau brute - Centiledrinking waterrequirement90 e centileValeur basée sur le 90e centile des valeurs observées pour le COT à l'eau brute.Eaux de surface.high
#P017physicalhealthmandatoryPériode de conformité de turbidité (RQEP)drinking waterMAC30 joursLa valeur limite qui, pour une période de 30 jours, doit être respectée.Conformément à l'article 5 de l'annexe 1 du RQEP.high
#P018physicalaestheticmandatoryCentile Couleur vraie (eau brute)drinking waterrequirement90 e centileValeur basée sur le 90e centile des valeurs observées pour la couleur vraie à l'eau brute.S'applique aux technologies de traitement en eau de surface.high
#P019operationalreportingmandatoryDélai maximal pour résultats de contrôle historiquesdrinking waterrequirement<= 60 joursRésultats des suivis de contrôle effectués jusqu'à 60 jours avant la date du dépôt du rapport de suivi de validation.Pour une demande de fiche de niveau Validé.high
#P020operationaloperationalmandatoryNombre total d'échantillonnages en période de pointedrinking waterrequirement20 échantillonnagesDurant les périodes où l'on atteindra les critères maximums, il y aura un échantillonnage par jour (quatre périodes de cinq jours).Suivi de validation (Niveau Validé) pour eaux de surface.high
#P021operationaloperationalmandatoryNombre total d'échantillonnages hors périodes de pointedrinking waterrequirement8 échantillonnagesDurant les autres mois, il y aura un échantillonnage par mois.Suivi de validation (Niveau Validé) pour eaux de surface.high
#P022physicaloperationalmandatoryPrécision du lecteur de turbiditédrinking waterrequirement0.01 UTNLecteur de turbidité (précis au centième d'UTN) pour le suivi des installations de filtration membranaire.S'applique aux équipements requis pour le suivi de la technologie de traitement par membranes.high
#P023chemicalhealthmandatoryPériode de calcul des sous-produits de chloration (THM et AHA)drinking waterrequirement4 trimestrescalculer la moyenne des valeurs maximales obtenues pour quatre trimestres consécutifs pour les trihalométhanes (THM) et les acides haloacétiques (AHA).Basé sur les exigences du RQEP citées dans la procédure.high
#P024operationalreportingmandatoryNombre minimal d'échantillons (Eaux de surface - Essais pilotes)drinking waterrequirement13 échantillonsL'échantillonnage pour les paramètres de base (pH, Température, E. coli, etc.) doit être effectué uniformément pendant toute la période d'essai.S'applique aux eaux de surface pour l'obtention d'une fiche de niveau En validation.high
#P025physicaloperationalmandatoryFréquence minimale de mesure - Transmittance UVdrinking waterrequirement>= 1 mesure aux deux semainesTransmittance UV de l'eau à 254 nm : Minimum et maximum annuel.Validation opérationnelle des réacteurs UV (Niveau Validé).high
#P026physicaloperationalmandatoryFréquence minimale de mesure - Température (UV)drinking waterrequirement>= 1 mesure hebdomadaireSuivi de la température de l'eau pour la validation opérationnelle des réacteurs UV.Validation opérationnelle des réacteurs UV (Niveau Validé).high
#P027chemicaltreatmentmandatorypH de l'essai de simulation SDS (Correction)drinking waterrequirement7.5 S.O.Conditions standard pour les essais SDS-THM et SDS-AHA.Essai de 24h avec chlore résiduel contrôlé.high
#P028designhealthmandatoryCertification des matériaux (NSF/ANSI 61)drinking waterrequirement61 NSF/ANSIles matériaux en contact avec l'eau utilisés par la technologie de traitement doivent être certifiés NSF/ANSI 61S'applique à toute technologie de traitement en eau potable soumise à validation.high
#P029designhealthmandatoryCertification des produits chimiques (NSF/ANSI 60)drinking waterrequirement60 NSF/ANSIles produits chimiques utilisés dans les technologies de traitement doivent être certifiés NSF/ANSI 60.S'applique à toute technologie de traitement en eau potable soumise à validation.high
#P030operationalreportingmandatoryAccréditation des laboratoires (ISO/CEI 17025)drinking waterrequirement17025 ISO/CEIl'analyse des échantillons prélevés... doit avoir été effectuée par un laboratoire accrédité selon la norme internationale ISO/CEI 17025Si les essais ont eu lieu ailleurs qu'au Québec.high
#P031operationalreportingmandatoryNombre minimal d'échantillons pH (Validation Surface)drinking waterrequirement28 échantillonsSuivi de validation avec des eaux de surface (Niveau Validé).Répartition : 1/semaine pendant 8 mois et 5/semaine pendant 4 mois.high
#P032microbiologicalhealthmandatoryNombre minimal d'échantillons E. coli (Validation Souterraine)drinking waterrequirement26 échantillonsSuivi de validation avec des eaux souterraines (Niveau Validé).Fréquence de 1 aux 2 semaines.high
#P033chemicalhealthmandatoryNombre minimal d'échantillons Nitrates/Nitrites (Pilote Surface)drinking waterrequirement3 échantillonsEssais pilotes avec des eaux de surface (Niveau En validation).Échantillonnage au début, au milieu et à la fin de la période de 13 semaines.high
#P034chemicaloperationalmandatoryParamètres critiques à l'eau brute (Eau souterraine) - Centiledrinking waterrequirement90 e centilevaleur basée sur le 90e centile des valeurs observées... pour tout paramètre jugé critiqueS'applique aux procédés de traitement utilisés en eau souterraine.high
#P035chemicaloperationalmandatoryAutres paramètres à l'eau brute (Eau souterraine) - Centiledrinking waterrequirement90 e centilevaleur basée sur le 90e centile des valeurs observées... pour tout paramètre jugé pertinentS'applique aux procédés de traitement utilisés en eau souterraine.high
#P036operationalreportingmandatoryNombre minimal d'échantillons (Eau souterraine - Essais pilotes)drinking waterrequirement13 échantillonsNombre minimal d'échantillons pour les paramètres de base (pH, Température, E. coli, etc.) en eau souterraine.S'applique pour l'obtention d'une fiche de niveau En validation.high
#P037operationalreportingmandatoryNombre minimal d'échantillons (Eau souterraine - Validation)drinking waterrequirement13 échantillonsNombre minimal d'échantillons pour les paramètres de base (pH, Temp, COT, etc.) en eau souterraine.Fréquence de 1 aux 4 semaines (Niveau Validé).high
#P038microbiologicalhealthmandatoryNombre d'échantillons haute fréquence (Eau souterraine - Validation)drinking waterrequirement26 échantillonsParamètres comme E. coli, coliformes, turbidité, dureté, fer, manganèse.Fréquence de 1 aux 2 semaines (Niveau Validé).high

D Definitions (7)

Req ID Category Name Context Confidence
#D001P0s1 er jet sans écoulement après au moins 6 heures de stagnationhigh
#D002P30saprès 30 secondes d ' écoulement continuhigh
#D003point d ' eau non conformeUn point d ' eau est non conforme si au moins une des teneurs en plomb, au premier jet (P0s) et après rinçage (P30s), est supérieure à 5 µg/L.high
#D004points d ' eau corrigésLes points d ' eau corrigés sont considérés conformes après vérification selon la procédure de dépistage appliquée.medium
#D005POEPoint-of-Entryhigh
#D006GACgranular activated carbonhigh
#D007the ProjectHiawatha First Nation Water Treatment System Upgradeshigh