| Req ID | Category | Intent | Legal Status | Name | Subdomain(s) | Context | Conditions | Confidence |
|---|---|---|---|---|---|---|---|---|
| #Q001 | operational | operational | guidance | Maintain minimal ammonia levels | drinking water | Although no health-based guideline value can be derived for ammonia in drinking water, it is still important to maintain minimal levels of ammonia in drinking water. | high |
| Req ID | Category | Intent | Legal Status | Name | Subdomain(s) | Limit Type | Limit Value | Context | Conditions | Confidence |
|---|---|---|---|---|---|---|---|---|---|---|
| #P001 | chemical | operational | guidance | free ammonia | drinking water | OG | < 0.1 mg/L | Limiting the excess of free ammonia entering the distribution system to concentrations below 0.1 mg/L... will help prevent nitrification. | entering the distribution system | high |
| #P002 | chemical | operational | recommended | free ammonia | drinking water | OG | < 0.05 mg/L | preferably below 0.05 mg/L, as ammonia-nitrogen, will help prevent nitrification. | entering the distribution system | high |
No definitions.