Parameter Viewer

Document ID ca-gcdwqgtd-2014-02-05-13 Title Guidelines for Canadian Drinking Water Quality: Guideline Technical Document – Turbidity URL https://www.canada.ca/en/health-canada/services/publications/healthy-living/guidelines-canadian-drinking-water-quality-turbidity/page-14-guidelines-canadian-drinking-water-quality-turbidity.html Jurisdiction /ca Subdomain(s) Drinking water, Water treatment Language en Status completed Analyzed at 2026-03-17 15:02:29.995126+00:00 Relevance Defines pathogen log removal credits for water treatment technologies.

Q Qualitative Requirements (7)

Req ID Category Intent Legal Status Name Subdomain(s) Context Conditions Confidence
#Q001treatmenttreatmentrecommendedMulti-barrier approach for physical log removal creditsdrinking waterUnder the multi-barrier approach to drinking water treatment, pathogen physical log removal credits should be used in conjunction with disinfection credits to meet or exceed overall treatment goals.Applicable when using physical log removal credits as part of a multi-barrier approachhigh
#Q002administrativeoperationalguidanceHigher log reduction credit approvaldrinking waterFacilities that believe they can achieve a higher log credit than is automatically given can be granted a log reduction credit based on a demonstration of performance by the appropriate regulatory agency.When facilities seek higher log credits than automatically assignedhigh
#Q003administrativeoperationalguidanceBag and cartridge filtration removal creditsdrinking waterNote: The values specified in section 1.0 do not apply to bag and cartridge filtration. Cryptosporidium and Giardia removal credit may be established by the responsible authority based on demonstration using challenge testing.When assessing removal credits for bag and cartridge filtrationhigh
#Q004operationaloperationalguidanceChallenge testing for bag and cartridge filter unitsdrinking waterChallenge testing is product specific; therefore, each manufacturer or third party can challenge test the filter unit to obtain a removal rating.high
#Q005monitoringoperationalmandatoryMembrane filtration log removal credit conditionsdrinking waterMicrofiltration, ultrafiltration, nanofiltration and reverse osmosis can receive log removal credit for Cryptosporidium , Giardia and nanofiltration and reverse osmosis can receive log removal credit for viruses if the process establishes a removal efficiency through challenge testing that can be verified by direct integrity testing and undergoes periodic direct integrity testing and continuous indirect integrity monitoring during use.To receive log removal credits for membrane filtration processeshigh
#Q006administrativereportingmandatoryMaximum removal credit for membrane filtrationdrinking waterThe maximum removal credit that a membrane filtration process is eligible to receive is equal to the lower value of either the removal efficiency demonstrated during challenge testing or the maximum log removal value that can be verified through the direct integrity test (i.e., integrity test sensitivity) used to monitor the membrane filtration processWhen calculating the maximum eligible removal credit for membrane filtrationhigh
#Q007administrativeoperationalguidanceLog removal credit thresholds for bag and cartridge filtrationdrinking waterUnder the U.S. EPA's LT2ESWTR, bag and cartridge filtration processes may receive a 1-log removal credit for Cryptosporidium for bag filtration that shows a minimum of 2-log removal in challenge testing and a 2-log removal credit for cartridge filtration showing a minimum of 3-log removal in challenge testing (U.S EPA, 2006b).Applicable when establishing removal credits for bag and cartridge filtration systems via challenge testinghigh

P Quantitative Requirements (21)

Req ID Category Intent Legal Status Name Subdomain(s) Limit Type Limit Value Context Conditions Confidence
#P001microbiologicaltreatmentguidelineCryptosporidium removal credit - Conventional filtrationdrinking watertreatment_goal3.0 logAverage potential removal credits estimated for Cryptosporidium when treated water meets the turbidity values specified in this guideline technical document.Conventional filtrationhigh
#P002microbiologicaltreatmentguidelineGiardia removal credit - Conventional filtrationdrinking watertreatment_goal3.0 logAverage potential removal credits estimated for Giardia when treated water meets the turbidity values specified in this guideline technical document.Conventional filtrationhigh
#P003microbiologicaltreatmentguidelineVirus removal credit - Conventional filtrationdrinking watertreatment_goal2.0 logAverage potential removal credits estimated for viruses when treated water meets the turbidity values specified in this guideline technical document.Conventional filtrationhigh
#P004microbiologicaltreatmentguidelineCryptosporidium removal credit - Direct filtrationdrinking watertreatment_goal2.5 logAverage potential removal credits estimated for Cryptosporidium.Direct filtrationhigh
#P005microbiologicaltreatmentguidelineGiardia removal credit - Direct filtrationdrinking watertreatment_goal2.5 logAverage potential removal credits estimated for Giardia.Direct filtrationhigh
#P006microbiologicaltreatmentguidelineVirus removal credit - Direct filtrationdrinking watertreatment_goal1.0 logAverage potential removal credits estimated for viruses.Direct filtrationhigh
#P007microbiologicaltreatmentguidelineCryptosporidium removal credit - Slow sand filtrationdrinking watertreatment_goal3.0 logAverage potential removal credits estimated for Cryptosporidium.Slow sand filtrationhigh
#P008microbiologicaltreatmentguidelineGiardia removal credit - Slow sand filtrationdrinking watertreatment_goal3.0 logAverage potential removal credits estimated for Giardia.Slow sand filtrationhigh
#P009microbiologicaltreatmentguidelineVirus removal credit - Slow sand filtrationdrinking watertreatment_goal2.0 logAverage potential removal credits estimated for viruses.Slow sand filtrationhigh
#P010microbiologicaltreatmentguidelineCryptosporidium removal credit - Diatomaceous earth filtrationdrinking watertreatment_goal3.0 logAverage potential removal credits estimated for Cryptosporidium.Diatomaceous earth filtrationhigh
#P011microbiologicaltreatmentguidelineGiardia removal credit - Diatomaceous earth filtrationdrinking watertreatment_goal3.0 logAverage potential removal credits estimated for Giardia.Diatomaceous earth filtrationhigh
#P012microbiologicaltreatmentguidelineVirus removal credit - Diatomaceous earth filtrationdrinking watertreatment_goal1.0 logAverage potential removal credits estimated for viruses.Diatomaceous earth filtrationhigh
#P013physicaloperationalunknownTurbidity (IESWTR 95th-percentile)drinking waterrequirement<= 0.3 NTUIESWTR turbidity requirements (combined filter effluent 95th-percentile value)Conventional filtration plants in compliance will achieve a minimum 2-log removal of Cryptosporidiummedium
#P014physicaloperationalunknownTurbidity (IESWTR maximum)drinking waterrequirement1.0 NTUIESWTR turbidity requirements (maximum value)Conventional filtration plantsmedium
#P015physicaloperationalunknownTurbidity (SWTR 95th-percentile)drinking waterrequirement<= 1 NTUTurbidity performance standards established under the 1989 Surface Water Treatment Rule (SWTR)Slow sand and diatomaceous earth filtrationmedium
#P016physicaloperationalunknownTurbidity (SWTR maximum)drinking waterrequirement5 NTUTurbidity performance standards established under the 1989 Surface Water Treatment Rule (SWTR)Slow sand and diatomaceous earth filtrationmedium
#P017physicaloperationalunknownTurbidity (SWTR 95th-percentile)drinking waterrequirement0.5 NTUCredits intended for a higher 95th-percentile turbidity performance standard recommended under the U.S. EPA's SWTR.Giardia and virus removal creditsmedium
#P018microbiologicaltreatmentguidelineCryptosporidium minimum removal in challenge testing - Bag filtrationdrinking waterrequirement2 logMinimum removal required in challenge testing to receive a 1-log removal credit.Bag filtrationhigh
#P019microbiologicaltreatmentguidelineCryptosporidium removal credit - Bag filtrationdrinking watertreatment_goal1 logRemoval credit received if showing a minimum of 2-log removal in challenge testing.Bag filtrationhigh
#P020microbiologicaltreatmentguidelineCryptosporidium minimum removal in challenge testing - Cartridge filtrationdrinking waterrequirement3 logMinimum removal required in challenge testing to receive a 2-log removal credit.Cartridge filtrationhigh
#P021microbiologicaltreatmentguidelineCryptosporidium removal credit - Cartridge filtrationdrinking watertreatment_goal2 logRemoval credit received if showing a minimum of 3-log removal in challenge testing.Cartridge filtrationhigh

D Definitions (0)

No definitions.