| #R001 | microbiological | health | unknown | E. Coli concentration threshold | drinking water | requirement | 49 CFU/100mL | Untreated water sample collected from Steele Springs Waterworks | Sample collected March 20, 2017 | high |
| #R002 | operational | reporting | recommended | Well inspection setback radius | drinking water | requirement | 0.5 km | Distance from the Steele Springs intake for identifying wells in the area of interest | Upgradient horizontal distance | high |
| #R003 | design | operational | unknown | Steele Springs intake burial depth | drinking water | requirement | 1.5 m | Screened pipe buried into sediment | Consistent positive pressure flow conditions | high |
| #R004 | design | unknown | unknown | Well 1 casing diameter | drinking water | requirement | 6 inches | Unregistered well located in a well pit | No well tag number found | high |
| #R005 | design | unknown | unknown | Well 4 casing diameter | drinking water | requirement | 4.5 inches | Domestic well in locked well house | Well Tag Number 31548 | high |
| #R006 | operational | health | recommended | Well 6 separation from horse pen | drinking water | requirement | 2 metres | Distance between wellhead and horse enclosure | Follow-up recommended further separation | high |
| #R007 | design | unknown | unknown | Well 5 casing diameter | drinking water | requirement | 27.0 cm | Outside irrigation well | No well ID plate | high |
| #R008 | design | unknown | unknown | Well 6 casing diameter | drinking water | requirement | 5 inches | Domestic well construction | No well identification plate | high |
| #R009 | design | unknown | unknown | Well 6 casing stick-up | drinking water | requirement | 29 inches | Stickup height from ground surface | Appropriate grading noted | high |
| #R010 | design | unknown | unknown | Well 6 total depth | drinking water | requirement | 180 ft | Depth below ground surface | Domestic well | high |
| #R011 | design | operational | unknown | Protective building footing depth | drinking water | requirement | 0.6 m | Depth of footings for concrete building over intake point | Reported as 2 feet by board members | high |
| #R012 | unknown | health | unknown | Manure observation distance | drinking water | requirement | 0.5 km | Distance of manure observed upslope from the collection point | Age of manure unknown | high |
| #R013 | operational | operational | unknown | Irrigation infrastructure distance | agricultural water | requirement | 0.5 - 1.0 km | Distance of irrigation pipe stickups from the Steele Springs intake | Beyond the inspection radius | high |
| #R014 | design | operational | unknown | Well 1 casing stick-up | drinking water | requirement | >= 48 inches | Stick-up height on well pit preventing direct surface flows | Unregistered well | high |
| #R015 | operational | operational | unknown | Well 2 distance to nearest water well | drinking water | requirement | > 15 m | Estimated distance to nearest water well | Private well inspection | high |
| #R016 | design | operational | unknown | Well 4 casing stick-up | drinking water | requirement | 2.25 inches | Stick-up height above floor level | Inside pump house | high |
| #R017 | operational | operational | unknown | Well 4 distance to nearest water well | drinking water | requirement | ~ 50 ft | Estimated distance to nearest water well | Private well inspection | high |
| #R018 | operational | health | mandatory | Wellhead maintenance setback | drinking water | requirement | 3 m | Regulatory requirement to keep area around wellhead clear of foreign matter | Mandatory maintenance under the Groundwater Protection Regulation (GWPR) | high |